Vulcan-Hart VPX5 Oven User Manual


 
– 4 –
INSTALLATION CODES AND STANDARDS
The steamer must be installed in accordance with:
In the United States of America:
1. State and local codes.
2. National Electrical Code, ANSI/NFPA-70 (latest edition). Copies may be obtained from The
National Fire Protection Association, Batterymarch Park, Quincy, MA 02269.
In Canada:
1. Local codes.
2. Canadian Electric Code, CSA C22.2 (latest edition). Copies may be obtained from The
Canadian Standard Association, 5060 Spectrum Way, Suite 100, Mississauga, Ontario,
Canada L4W 5N6.
LEVELING
The steamer must be level for proper operation. Place a carpenter's level on top of the steamer.
Level the steamer front to back and side to side by turning the adjustable feet.
ELECTRICAL CONNECTIONS
WARNING: ELECTRICAL AND GROUNDING CONNECTIONS MUST COMPLY WITH THE
APPLICABLE PORTIONS OF THE NATIONAL ELECTRICAL CODE AND/OR OTHER LOCAL
ELECTRICAL CODES.
When making electrical connections, use copper wire suitable for at least 200°F (90°C). The
steamer must be grounded. The wiring diagram is located on the inside of the right panel.
Steamers wired for 1 phase can be changed to 3 phase or vice versa by relocating the jumper wires
on the terminal block as shown on the wiring diagram.
ELECTRICAL DATA
Model Volts KW Amp @ 1 PH Amp @ 3 PH
208
6 28.9 NA
9 43.3 25
VPX3 240
625 NA
9 37.5 21.7
480
6 12.5 NA
9 18.8 10.9
208
10 48.1 NA
15 72.2 41.7
VPX5 240
10 41.7 NA
15 62.5 36.1
480
10 20.9 NA
15 31.3 18.1