Wind Crest CTG365D Cooktop User Manual


 
3
1. For your safety:
-Do not obstruct the flow of combustion and ventilation air to the unit.
-Keep appliance area clear and free from combustible material.
2. Never use this product for warming or heating a room.
3. An approved gas regulator is supplied and should be used with this appliance.
POWER SUPPLY Requires a 120 VAC, 60 HZ, 15 Amp single-phase circuit for all models. A three prong grounded
receptacle is required. Plan the installation for the unit so that the location of the three-prong
receptacle is within three (3) feet of the right rear bottom corner of the cooktop and accessible from
the front of the cooktop. See FIG 6.
Warning - The grounding prong must not be cut or removed from the power cord.
- A three prong grounded receptacle must be used.
- The power source must be properly polarized. Reverse polarity w
ill cause continuous sparking of the
electrodes.
- Do not use a Ground Fault Circuit Interrupter (GFCI). The electrode
spark ignition module will cause GFCI’s to trip.
This appliance, when installed, must be electrically grounded in accordance with local codes, or in the absence of local
codes, in accordance with National Electric Code ANSI/NFPA 70. The correct voltage, frequency and amperage must be
supplied to the appliance from an individual, dedicated grounded circuit which is protected by a properly sized circuit
breaker or time delay fuse. The required voltage, frequency and amperage ratings are listed on the product data plate and
also shown above.
This appliance is factory equipped with a 5-foot long power supply cord having a 3-prong grounded plug. This plug must
be inserted into a mating grounded receptacle in accordance with National Electrical Code and applicable state, municipal
and local codes.
In Canada, installation must be in accordance with CSA C22.1 Canadian Electrical Code Part-1 and/or local codes.
GAS SUPPLY PRESSURE NATURAL GAS: 6 to 14 inches water column (Manifold at 4-inches)
PROPANE GAS: 11 to 14 inches water column (Manifold at 10-inches)
CAUTION: For LP gas installations, the LP gas tank must have its own high pressure
regulator. This is in addition to the pressure regulator supplied with the cooktop.
Check your local building codes for the proper method of installation. In the absence of local codes, this appliance should
be installed in accordance with the National Fuel Gas Code ANSI Z223.1. Be certain that the appliance being installed is
correct for the gas service provided. Refer to the data plate located on the bottom of the cooktop and pressure
requirements above.
In Canada, installation must be in accordance with current CAN/CGA B149.1 and 2 gas installation codes and/or local
codes.
NOTE: The cooktop settings for natural gas are established at the factory. No field adjustments are required.
Natural gas cooktops can be converted for Liquid Propane (LP) use by qualified servicers only. A factory supplied
“LP” conversion kit is available. To obtain kit contact your local dealer.
MODEL CTG304D LP KIT #10691.00
MODEL CTG305D LP KIT #10692.00
MODEL CTG365D LP KIT #10693.00