.
NOTE: Unit must be vented
to outside of the building.
Prepare cabinet for mounting the hood per FIG-2. Use
furring strips to level cabinet mounting surface with any
cabinet trims. If your hoods accepts and your using dual
internal ventilators refer to that instruction section.
Attach and secure the transition to the hood with #6x3/8
sheet metal screws and tape all joints prior to installing the
hood. Attach hood to cabinet using #10 wood screws.
Holes are located in the back panel and top panel of the
hood for mounting. Use a minimum of four #10x3/4 wood
screws to mount the hood. Longer screws are required if
wall board or other nonstructural surfaces are used
between the hood and main mounting surface which
holes for additional mounting use appropriate anchors if
not engaging the wood structure.
HINT: If you find vibration noise is present because of
cabinet structure use additional screws, in holes available,
to rigidize mounting.
Connect 120 volt, 60 Hz power through the conduit hole
in top of hood, connecting to pigtail in hood junction box,
white to white, black to black and connect green ground
wire to the power supply ground wire per local codes.
The recommended height from countertop or cooking
surface to the bottom edge of the hood is 30 to 36 inches.
Hood is recommended for use over domestic gas or
electric appliances. Not recommended for use over solid
fuel fired appliances.
After installing the hood, install the internal blower
(see FIG-1) unit by positioning the blower onto
bracket-A, notched blower bracket will center
blower. Rotate into position against hood top and
secure with #8 sheet metal screws via bracket-B. To
ease assembly you should predrive and then remove
the #8 screws before installing the blower. If the
remote ventilator is used see related instructions. The
VEN100E/140E ventilator will require revision of
some wiring in the hood receptacle box and possible
modification of air discharge opening See
VEN100E/140E instructions.
NOTE: VEN140E requires a 20 AMP Power Supply.
CAUTION: The hood is of sufficient weight that two
installers are recommended to prevent injury or damage to
the hood in handling.
Turn the power on at the service entrance and check the
operation of the controls.
NOTE: be sure that all dampers are operating properly and
are free to open.
BACKDRAFT DAMPER
: It is recommended that a backdraft damper be used
in all installations. In cold weather installations it is necessary to use a backdraft
damper to minimize backflow of cold air into room. A non-metallic thermal
break should also be used to minimize conduction of outside temperatures
through the ductwork. The thermal break should be located as close as possible
to where the ducting enters the heated portion of the house.
SAFTY WARNING:
Turn off power circuit at
the service entrance and
lockout panel before
wiring the range hood.