A SERVICE OF

logo

Turbomachinery Package Specification Taurus 70 Compressor Set and Mechanical Drive
Purchaser piping and instrumentation diagram including suction and recycle
pipe size and schedule
Anti-surge control (recycle) valve and specification sheet, unless included in
Solar's scope
Suction and discharge gas temperature signal (100-ohm platinum resistance
temperature devices (RTDs) preferred)
Typical system scope includes the following:
Engineering to determine the optimum control algorithms
Control software programmed and tested for the selected gas compressor
staging
Engineering to specify the anti-surge control valve and accessories, including
valve performance evaluation over the gas compressor performance map at
varying valve positions
Engineering to specify the flow meter type and size
Automatic override of manual control mode
Evaluation of user piping and instrumentation diagram
Documentation, including all surge control calculations and program constants
Gas compressor flow versus differential pressure control with suction pressure
and temperature compensation
Speed set point decoupling
Surge detection with step valve opening
On-screen, real-time graphic displays
On-screen, real-time control parameter setting
All surge control parameters are available for remote monitoring via serial link
11.1.5 Anti-Surge Recycle Valve
When included in Solar’s scope of supply, the anti-surge recycle valve is supplied as a
complete and functionally tested assembly, shipped separately for field installation. The
assembly includes the valve and the following accessories and features:
Spring-return, diaphragm-type, pneumatic actuator
Position transmitter with valve fully open and fully close relay outputs and 4-to-
20 mA proportional to percentage closed
Pressure regulator
3-way 24-VDC solenoid valve
Electropneumatic valve positioner
½-in. NPT actuator pressure port
Carbon steel body per ASTM A352
Interconnecting 316L stainless steel tubing and compression-type fittings
Temperature Limits:
Process gas:
- 6.7° to 218°C (20° to 425°F)
Ambient:
-28.9° to 60°C (-20° to 140°F)
The assembly requires clean, dry regulated air or natural gas, 552 to 862 kPag (80 to 125
psig),
-28.9° to 60°C (-20° to 140°F), dew point -40°C (-40°F)
© 2009 Solar Turbines Incorporated. All rights reserved. TPS70CSMD/309
45