Server Power Cords
One 6' Highline (IEC-IEC) power cord ships standard
NOTE:
HP ProLiant DL servers no longer ship standard with NEMA power cords (163719-002)
that allow connection to 110V US wall outlets in a home or office. ProLiant DL servers are
primarily connected to PDU's in data center racks so they now ship standard with only a PDU
power cord (416151-B21). If a user wishes to power a ProLiant DL server using a 110V receptacle
(NEMA-15), the NEMA power cord (227099-001) must be ordered separately.
If customers require a local power cord, they can check the power cord matrix for the appropriate
cord. Please see the following power cord matrix:
http://www.hp.com/go/powercordmatrix
.
UPS and PDU Power
Cord Matrix
Please see the UPS and PDU cable matrix that lists cable descriptions, requirements, and
specifications for UPS and PDU units:
http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/index.html
.
Power Supply
650 Watts, auto-switching, PFC (Power Factor Correcting)
NOTE:
Factory upgradeable to high-efficiency (HE) power supply for lower TCO
System Fans
6 system fans ship standard; Non-hot plug, Non-redundant
OS Support
Microsoft Windows Server 2003 R2
Microsoft Windows Server 2008
Microsoft Windows Small Business Server 2008
Microsoft Windows Essential Server 2008
Red Hat Enterprise Linux
SUSE Linux Enterprise Server
Sun Solaris for x64/x86-based Systems
NOTE:
For more information on HP's Certified and Supported ProLiant Servers for OS and
Virtualization Software and latest listing of software drivers available for your server, please visit
our Support Matrix at:
http://www.hp.com/go/supportos
and our driver download page
http://www.hp.com/support/DL160G5
.
Rack Airflow
Requirements
Rack 10000 series Cabinets
The increasing power of new high-performance processor technology requires increased cooling
efficiency for rack-mounted servers. The 10000 Series Racks provide enhanced airflow for
maximum cooling, allowing these racks to be fully loaded with servers using the latest processors.
CAUTION:
If a third-party rack is used, observe the following additional requirements to ensure
adequate airflow and to prevent damage to the equipment:
Front and rear doors: If your 42U server rack includes closing front and rear doors, you must allow
5,350 sq cm (830 square inches) of hole evenly distributed from top to bottom to permit adequate
airflow (equivalent to the required 64 percent open area for ventilation).
Side: The clearance between the installed rack component and the side panels of the rack must
be a minimum of 7 cm (2.75 inches)
CAUTION:
Always use blanking panels to fill all remaining empty front panel U-spaces in the rack.
This arrangement ensures proper airflow. Using a rack without blanking panels results in improper
cooling that can lead to thermal damage.