Page 176 Specifications 51-52-25-150, Issue 1 – April 2009
mV ranges : >10MΩ.
Voltage ranges: 47KΩ.
Curent ranges: 5Ω.
Voltage input: will withstand up to 5x input voltage overload without
damage or degradation of performance in either polarity.
Current input: will withstand 5x input current overload in reverse
direction and up to 1A in the normal direction.
Reinforced safety isolation from outputs and inputs (except to Digital
Input B).
Detection:
Applicable for 4 to 20mA, 1 to 5V and 2 to 10V ranges only.
Control goes to the pre-set power value if Auxiliary Input is providing the
active setpoint source.
Digital Inputs
Digital Input Functions
Hold Running Profile Run or release selected profile
No Action
Release from Hold Segment
No Action
Abort Running Profile
Stop Recording Start Recording
Select Local Setpoint 1 Select Alternate Setpoint
Automatic Control Mode Manual Control Mode
Enable PID Control Outputs Disable PID Control Outputs
The above actions apply if a digital input has been defined to control the specified function(s)
Digital Input Performance
Voltage-free or TTL-compatible.
Connection to contacts of external switch or relay:
Open = Logic High. Minimum contact resistance = 5KΩ,
Closed = Logic Low. Maximum contact resistance = 50Ω.
2.0 to 24VDC = Logic High.
–0.6 to 0.8VDC = Logic Low.
Digital Input Sensitivity:
Edge Sensitive. Requires High-Low or Low-High transition to
change function.
Response within <0.25 second of signal state change.