14 Installation (for qualified installers only)
© Travis Industries 4090717 100-01225_000
Vertical Terminations with Zero, Two, or Four 45° Elbows
10’ Minimum System
Height
(with or without offsets)
40’ Maximum System
Height
24’ Maximum Offset
The termination must fall
within the shaded area
shown in the chart. Use
the indicated restrictor
position.
5 feet (1.5m)
10 feet (3m)
15 feet (4.5m)
20 feet (6m)
25 feet (7.5m)
30 feet (9m)
0 feet
40' max (12m)
5 feet (1.5m)
0 feet
0 feet
5 feet (1.5m)
10 feet (3m)
15 feet (4.5m)
20 feet (6m)
25 feet (7.5m)
30 feet (9m)
40' max (12m)
Restrictor
Position # 5
NOTE:
Restrictor positions are based
upon lab tests. The ideal
restrictor position may vary
slightly, especially when the
termination is near a
demarkation line.
Restrictor
Position # 6
10 feet (3m)
15 feet (4.5m)
20 feet (6m)
24 ' max (7.3m)
0 feet
5 feet (1.5m)
10 feet (3m)
15 feet (4.5m)
20 feet (6m)
24 ' max (7.3m)
35 feet (10.5m)35 feet (10.5m)