Menu 0 Parameters D-17
0.27 Motorized potentiometer
zero-start select
RW Bit
0 ~ 1 0
Applicable to Macros...
01234567
Set 0.27 for the way the motorized potentiometer
is to behave at power-up of the Drive as follows:
0 The motorized-potentiometer output returns to
the value it held when the Drive was previously
powered-down
1 The motorized-potentiometer output starts at
zero
0.27 Analog reference 2
RO Bi
±100
%
Applicable to Macros...
01234567
0.27 indicates the value of analog input 2 as a
percentage of the full-scale value.
Analog input 2 is used for the frequency reference
when Macro 4 is being used in frequency control. In
this case, analog input 2 is not used for torque
control.
0.28 EUR> Current-loop
proportional gain
RW Uni
0 ~ 30 000 20
Applicable to Macros...
01234567
Do not adjust this parameter.
0.28 Motorized potentiometer
bipolar select
RW Bit
0 ~ 1 0
Applicable to Macros...
0123
4
567
Set 0.28 as follows:
0 Unipolar output (0 ~ 100%)
1 Bipolar output (±100%)
0.28 USA> Frequency demand
RO Bi P
±1000
HZ
Applicable to Macros...
0123
4
567
USA configuration
0.28 differs from 0.11 Pre-ramp reference in that it
indicates the demanded reference before frequency
limiting and skip bands.