6.1.3 Program examples
Examples of single flows
1. Example of flicker circuit
When the PLC mode is changed from STOP to RUN, the state relay S3 is driven by the initial pulse
(M8002).
The state relay S3 outputs Y000. One second later, the ON status transfers to the state relay S20.
The state relay S20 outputs Y001. 1.5 seconds later, the ON status returns to the state relay S3.
1 second 1.5 second
Y000
Y001
[Structured ladder/FBD]
[ ST ]
SET(M8002,S3);
STL(TRUE, S3);
Y000:=TRUE;
OUT_T(TRUE, TC0,K10);
SET(TS0, S20);
STL(TRUE, S20);
Y001:=TRUE;
OUT_T(TRUE, TC1, K15);
S3:=TS1;
RET(TRUE);
M8002
Initial
pulse
Y000
S3
STL
EN ENO
s
SET
EN ENO
d S3
Y001
S20
STL
EN ENO
s
S3
OUT_T
EN ENO
TC0
TCoil
TValue
K10
TS0
SET
EN ENO
d S20
OUT_T
EN ENO
TC1
TCoil
TValue
K15
TS1
RET
EN ENO
Step
number
0
3
8
11
16
19