Regency Wood Insert & Hearth Heater 7
Clearance diagram for installations
INSTALLATION
Side and Top facing is a maximum of 1.5"
thick.
Floor protection must non-combustible, insula-
tive material with an R value of 1.1 or greater.
* If the hearth extension is ush with the oor
(F) it must extend 19.5" in front of the body
face (E).
Note: Hearth Extension Width (G) is meas-
ured from edge of fuel door to side
of hearth.
** A non-combustible mantel may be in-
stalled at a lower height if the framing
is made of metal studs covered with a
non-combustible board.
MASONRY AND FACTORY BUILT FIREPLACE CLEARANCES
The minimum required clearances to combustible materials when installed into a masonry or factory built replace are listed below.
View from Rear of Insert
OPTIONAL FLUE
CONNECTOR KIT
The optional Flue Connector Kit (Part # 846-527)
and the Straight Flue Adaptor (Part #846-504)
shown here, may be used to produce a secure
connection between your ue connector and the
insert collar. Detailed installation instructions are
included with the kit.
Position the grill on the inside bodyface side and
fasten using the bolts, washers and nuts provided
(2 per side) as shown in the diagrams.
Note: The grill has a front and rear, the holes
on the front side have rounded edges
and the rear holes have at edges.
Adjacent Mantle** Top Side Minimum Minimum Minimum
Unit Side Wall (to Top) Facing Facing Hearth Hearth Hearth Side
(to Side) (to Top) (to Side) Extension* Thickness* Extension
A B C D E F G
Large Flush
Insert (I3100L) 13"/330mm 19"/480mm 18"/455mm 6.5"/165mm 16"/406mm 1.5"/38mm 8"/205mm
Hearth Heater
(H2100M) 10"/255mm 25"/635 mm 14"/355mm 8.5"/216mm 18"/455mm 1.5"/38mm 6"/152mm
Thermal oor protection is not required if the
unit is raised 3.5" minimum (measured from
the bottom of the stove). However, standard
ember oor protection is required. It will need
to be a non-combustible material that covers
16" (406 mm) in the US and 18" (450 mm)
in Canada to the front of the unit and 8" (200
mm) to the sides.
If the unit is not raised, thermal oor protec-
tion required is 18" (450 mm) in the US and
Canada.