■ PV calibration
Scroll ↑, ↓, ←, or → keys to show (
1.0.1.1.
) on upper display, then press ENT
key.
●Gain No. select
Press PARA key until the PROG/SEG display shows (01-01). Connect calibration
device (See Section “11-3 Set Up”).
Input the gain number (See Table 11-9 and Table 11-10) by scrolling ↑, ↓, ←, or →
keys the upper display ( ENT key not required).
●PV zero, span
(1) PV zero adjustment
(a) Press PARA key until the PROG/SEG display shows (
01-02
).
(b) Adjust your calibration device to an output signal equal to the 0% range value
(See Table 11-9), the signal need to be on the input for 10 to 15 seconds.
(c) Press ENT key after display stabilizes.
(2) PV span adjustment
(a) Press PARA key until the PROG/SEG display shows (
01-03
).
(b) Adjust your calibration device to an output signal equal to the 100% range value
(See Table 11-9 and table 11-10).
(c) Press ENT key after display stabilizes.
Table 11-9.
Table 11-10.