1600EP Series Quick Installation Guide
4
Wire Size and Tightening Torque
Use the following table to select the recommended wire size and terminal lug tightening torque for I/O wire connections.
Item
Terminal
Number
AWG
3.6-RoHS kVA
AWG
3.6 kVA
AWG
6 kVA
AWG
8 kVA
AWG
10 kVA
AWG
14-18 kVA
AWG
22 kVA
Tightening
Torque
lb.-in. (N•m)
AC Input Lines 1 and 2 12 (8) 12 (8)
10 (8) 8 (1/0) 6 (1/0) 4 (1/0) 1 (1/0)
14.2 (1.56)
AC Output Lines 4, 5, and 7 12 (8) 12 (8)
10 (8) 8 (1/0) 6 (1/0) 4 (1/0) 1 (1/0)
14.2 (1.56)
AC Output Neutral 6 12 (8) 12 (8)
10 (8) 8 (1/0) 6 (1/0) 4 (1/0) 1 (1/0)
14.2 (1.56)
Ground 3 and 8 12 (8) 12 (8)
10 (8) 8 (1/0) 6 (1/0) 4 (1/0) 1 (1/0)
14.2 (1.56)
EPO Switch 14 and 15 16 16 16 16 16 16 16 9.0 (0.99)
Remote Switch 16 and 17 16 16 16 16 16 16 16 9.0 (0.99)
Note: Wire size presented as the recommended size followed by a bold number in () that is the maximum wire size the terminal block can
accommodate. See the manual, page 48, for knock-out hole sizes on the back of each model.
FAQs
Below are some Frequently Asked Questions concerning installation of the 1600EP Series UPS.
The batteries for the UPS must be installed while the UPS is energized.
FAQ #1 My Output is ~85V.
Problem: Output is wired across the incorrect output terminals. The voltage across terminals 5 – 6(X2 – N) will
be approximately 85V.
Solution: The correct 120V output terminals are 4 – 6 (X1 – N), and 7 – 6 (X3 – N).
FAQ #2 My Output is other than 85, 120, 208 or 240V in Bypass mode.
Problem: The Terminal strip jumper may be installed incorrectly for the incoming voltage.
Solution: Check that the Jumper wire/buss strip is installed correctly for the incoming voltage.
Toshiba Contact Information: Toshiba Industrial Division, 13131 West Little York Road, Houston, TX 77041
Tel: US 800-231-1412, Canada 800-872-2192, Mexico 01/800/527-1204 www.toshiba.com/ind