40 LonTalk Communication Interface • ACC-SVN100A-EN
Network Variable and Configuration Property Definitions
nvoHiSideOilPrsX
High side oil pressure—compressor X,* SNVT_press_f
nvoHiSideOilPrsA
nvoHiSideOilPrsB
nvoHiSideOilPrsC
nvoHiSideOilPrsD
nvoHiSideOilPrsE
nvoHiSideOilPrsF
This network variable measures the pressure of the oil at the high-pressure side of
compressor X (*where X = A, B, C, D, E, or F, depending on the network variable). There
are separate network variables for each compressor.
• Default: NaN
• Invalid value: NaN
nvoLoSideOilPrsX
Low side oil pressure—compressor X,* SNVT_press_f
nvoLoSideOilPrsA
nvoLoSideOilPrsB
nvoLoSideOilPrsC
nvoLoSideOilPrsD
nvoLoSideOilPrsE
nvoLoSideOilPrsF
This network variable measures the pressure of the oil at the low-pressure side of
compressor X (*where X is A, B, C, D, E, or F, depending on the network variable). There
are separate network variables for each compressor.
• Default: NaN
• Invalid value: NaN
nvoLvgChWTemp
Evaporator leaving water emperature, SNVT_temp_p
This network variable provides the temperature of the water leaving the evaporator.
• Default: 0x7FFF = 327.67°C
• Invalid value: 0x7FFF = 327.67°C
nvoLvgCndWTemp
Condenser leaving water temperature, SNVT_temp_p
This network variable provides the temperature of the water leaving the condenser.
• Default: 0x7FFF = 327.67°C
• Invalid value: 0x7FFF = 327.67°C