Line-interactive voltage regulation maintains selectable 120V nominal output during brownouts as low as 95V and overvoltages to 145V
Enables continuous operation through blackouts, voltage fluctuations and surges
Line-interactive automatic voltage regulation (AVR) provides 14% voltage boost during brownouts and a 12% voltage cut during
overvoltages
Standard internal battery set offers 16 min. runtime at half load (490W) and 6.75 min. at full load (980W)
Runtime is expandable with the addition of BP36V15-2U (limit 1) or BP36V42-3U external battery packs
Space-saving upright tower format
Network interfaces support simultaneous communications via built-in USB port, DB9 serial port and SNMPWEBCARD slot HID-compliant
USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X.
Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus
any number of additional servers over IP
UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current,
battery capacity, timed inverter shutoff, activate self-test and output power control
NEMA 5-15P input plug / 8 x NEMA 5-15R output receptacles
Front panel LEDs offer current monitoring, voltage regulation and battery charge level information
UPS ships fully assembled in full compliance with DOT regulations; no time-consuming connection of internal batteries by user required
Single-line tel/DSL or network Ethernet line surge suppression (POE compatible)
2-year product warranty; $250,000 Ultimate Lifetime Insurance (USA, Puerto Rico, Canada)
Specifications
SYSTEM OVERVIEW
Voltage compatibility 120V
Frequency
compatibility
60Hz
OUTPUT
Output VA 1500
Output watts 980
Output nominal
voltage
120V
Output voltage
regulation
LINE MODE: Sine wave line voltage 120V (-12%/+14%), BATTERY MODE: Sine wave output 120V (+/-5%)
Output frequency
regulation
LINE MODE: Passes line frequency of +/-10% BATTERY MODE: Inverter output regulated to 60Hz (+/- 1Hz)
Outlet quantity / type 8 NEMA 5-15R
INPUT
Maximum input
amps
9.8A
Input connection
type
NEMA 5-15P
Input cord length 6ft., 1.8m
Recommended
Electrical Service
15A 120V
BATTERY
Full load runtime 6.75
Half load runtime 16
DC system voltage 36V DC
Typical battery
lifespan
4-6 years typical
Battery recharge rate 4-8 hours to 90%
Replacement
Battery Cartridge
RBC53
VOLTAGE REGULATION