A SERVICE OF

logo

Frequency
compatibility
60 Hz
Frequency
compatibility details
Output frequency regulation +/-0.05Hz (free running)
Output voltage
regulation (line mode)
+/- 2%
Output voltage
regulation (Economy
line mode)
+/- 10%
Output voltage
regulation (Battery
mode)
+/- 2%
Built-in UPS output
receptacles
4 5-15R outlet(s); 8 5-15/20R outlet(s); 2 L6-20R outlet(s); 2 L6-30R outlet(s)
Output receptacle
details
Output receptacles and input line cord are mounted on a detachable PDU backplate with bypass switch to enable
hot-swappable power module replacement
Output circuit breaker High voltage 20A breaker protects L6-20R outlets, L6-30R outlets are unbreakered; Low voltage 20A breakers
protect 4 5-15/20R outlets each; Low voltage 15A breakers protect 2 5-15/20R outlets each
Output AC waveform
(AC mode)
Pure Sine wave
Output AC waveform
(battery mode)
Pure Sine wave
INPUT
Rated input current
(at maximum load)
31.9A (200V), 30.6A (208V), 29A (220V), 27.7A (230V), 26.6A (240V)
Nominal Input
Voltage(s) Supported
208V AC; 240V AC
Nominal input
voltage description
Factory configured to 208V
UPS input
connection type
L6-30P
UPS Input cord
length (ft.)
10
UPS Input cord
length (m)
3
Recommended
Electrical Service
30A
Phase Single-Phase
BATTERY
Full load runtime
(minutes)
2 min. (5400 watts)
Half load runtime
(minutes)
8.5 min. (2700 watts)
Expandable battery
runtime
Runtime is expandable with external battery packs
External battery pack
compatibility