Alto-Shaam QC2-40 Freezer User Manual


 
QUICKCHILLER • MN-29647 (REV. 0) • INSTALLATION/OPERATION/SERVICE MANUAL • 12.
SUB TITLE
TITLE
ELECTRICAL
INSTALLATION
This appliance must be branch circuit protected with
proper ampacities, in accordance with the wiring
diagram. The Quickchiller must be properly grounded
in accordance with the National Electrical Code
and applicable local codes. Wire size for the main
incoming power to the unit must match the minimum
size listed in the specifications applicable to the
specific Quickchiller model. For supply connections,
locate the wire size listed in this manual.
Before operating the chiller, check all cable connections
in the electrical connection area for tightness since
connections can loosen during transport.
NOTE: 





danger
To avoid electrical shock, this
appliance MUST be adequately
grounded in accordance with local
electrical codes or, in the absence of
local codes, with the current edition
of the National Electrical Code ANSI/
NFPA No. 70. In Canada, all electrical
connections are to be made in
accordance with CSA C22.1, Canadian
Electrical Code Part 1 or local codes.
danger
ELECTRICAL CONNECTIONS MUST
BE MADE BY A QUALIFIED SERVICE
TECHNICIAN IN ACCORDANCE WITH
APPLICABLE ELECTRICAL CODES.
voltage phase cycle/hz
QC2-3 QC2-20 QC2-40 QC2-100
QC2-100R
remote
115 1 ph 60 Hz
recommended circuit amperage:
plug configuration:
16A, 1.8kW
20 amps
NEMA 5-20P
16A, 1.8kW
20 amps
NEMA 5-20P
not available not available not available
115/208-230 1 ph 60 Hz
recommended circuit amperage:
plug configuration:
not available not available
16A, 3.7kW
20 amps
NEMA 14-20P
24A, 5.5kW
30 amps
4 wire direct
20A, 4.6kW
30 amps
4 wire direct
115/208-230 3 ph 60 Hz
recommended circuit amperage:
recommended wire size:
not available not available not available
16A, 3.7kW
20 amps
5 wire direct
not available
220 1 ph 50 Hz
recommended circuit amperage:
recommended wire size:
not available
14A, 1.8kW
20 amps
3 wire direct
20A, 4.4kW
30 amps
5 wire direct
20A, 4.4kW
30 amps
3 wire direct
16A, 3.5kW
20 amps
3 wire direct
380-420 3 ph 50 Hz
recommended circuit amperage:
recommended wire size:
not available not available
10A, 3.8kW
20 amps
5 wire direct
12A, 4.6kW
20 amps
5 wire direct
7A, 2.7kW
15 amps
5 wire direct
ELECTRICAL SPECIFICATIONS
Wire diagrams are located near the top of the
unit, close to the compressor or control panel.