Amana HRV-200 Ventilation Hood User Manual


 
4
Dimensions
A
B
CD
E
5
TH
port for recirculation defrost type models only
0
0.2
0.4
0.6
0.8
1
1.2
0
50
100
150
200
250
300
40080
SHR(D) 1505RSHR(D) 1505R
SHR(D) 2005R
120 160
Airflow (cfm)
Airflow (L/s)
Static Pressure (in WC)
Static Pressure (Pa)
200 240
190 38 57 76 94
114
Fresh Air
From Outside
Stale Air
To Outside
Fresh Air
To Inside
Stale Air
From Inside
5
TH
port for recirculation defrost models
only can be ducted or left open
Airflow
HRV-150D & HRV-200D
Model A B C D E
HRV-150D 2 ¹⁄₄" (56mm) 23 ¹⁄₂" (596mm) 2 ⁵⁄₈" (67mm) 17 ³⁄₈" (441mm) 17 ³⁄₈" (441mm)
HRV-200D 2 ¹⁄₄" (56mm) 27 ⁷⁄₈" (707mm) 2 ⁵⁄₈" (67mm) 17 ³⁄₈" (441mm) 20 ¹⁄₂" (520mm)
Fan Performance
Performance Data
Model
HRV-150D 72 % 69 %
HRV-200D 71 % 76 %
Apparent Sensible
Effectiveness at
32ºF (0ºC)
Apparent Sensible
Effectiveness at -
13ºF (-25ºC)
AIRFLOW CAP. cfm (L/s) @ 0.4 on High Speed
Power
• Volts 120 VAC
• Amperage
HRV-150D 1.5 Amps Total
HRV-200D 1.9 Amps Total
• Phase Single Phase
6"
HRV-200D
HRV-150D