American Power Conversion 30RAN035 Refrigerator User Manual


 
Supplemental Installation Information for APC Chillers 5
Dual Power Feature (Optional)
The optional dual power feature provides a separate power connection point for the pumps and
controls. If the circuit is connected to an Uninterruptible Power Supply (UPS), the power connection
keeps the pumps running to recirculate cooling water in the event of a power failure.
Upon loss of power, all compressors and fans shut down. At the same time, the dual-power relay
closes, putting the unit in heat mode, allowing the controller to keep the pumps running and also
removes any call for cooling.
On power restoration, the dual power relay opens. The unit returns to cooling mode and stages up
compressors as required.
See the electrical schematics included in this packet containing electrical data on the power feeds for
the pumps and chiller.