American Power Conversion 30RAN035 Refrigerator User Manual


 
6 Supplemental Installation Information for APC Chillers
Power Requirements
APC Model
No
Main Power Supply
Dual Power Supply for Pumps and
Controls
Pump
LRA
Volts AC
PH
Hz
Max Volts
Min Volts
MCA
MOCP
FLA
Volts AC
PH
Hz
Max Volts
Min Volts
MCA
MOCP
FLA
ACCH050G-
AKA-D03S
460 3 60 506 414 37.3 60 33.3
ACCH084G-
AKA-D03S
460 3 60 506 414 54.0 70 50.9
ACCH120G-
AKA-D05S
460 3 60 506 414 79.5 100 75.5
ACCH167G-
AKA-D05S
460 3 60 506 414 101.8 110 98.7
ACCH050G-
ADA-D03S
460 3 60 506 414 33.6 50 29.6 460 3 60 506 414 15.0 15 5.7 28.5
ACCH084G-
ADA-D03S
460 3 60 506 414 50.3 70 47.2 460 3 60 506 414 15.0 15 5.7 28.5
ACCH120G-
ADA-D05S
460 3 60 506 414 73.2 90 69.2 460 3 60 506 414 15.0 15 8.3 65.0
ACCH167G-
ADA-D05S
460 3 60 506 414 95.5 110 92.4 460 3 60 506 414 15.0 15 8.3 65.0
ACCH050G-
ABA-D03S
208/
230
3 60 253 187 77.5 125 69.3
ACCH084G-
ABA-D03S
208/
230
3 60 253 187 110.6 150 104.4
ACCH120G-
ABA-D05S
208/
230
3 60 253 187 167.3 200 159.1
ACCH167G-
ABA-D05S
208/
230
3 60 253 187 208.6 225 198.3
ACCH050G-
AAA-D03S
208/
230
3 60 253 187 69.3 110 59.1 208/230 3 60 253 187 15.0 15 10.2 60.0
ACCH084G-
AAA-D03S
208/
230
3 60 253 187 102.4 125 94.2 208/230 3 60 253 187 15.0 15 10.2 60.0
ACCH120G-
AAA-D05S
208/
230
3 60 253 187 153.4 200 143.2 208/230 3 60 253 187 17.4 30 15.9 138.8
ACCH167G-
AAA-D05S
208/
230
3 60 253 187 194.6 225 186.4 208/230 3 60 253 187 17.4 30 15.9 138.8