Carrier 30GT-911---062 Refrigerator User Manual


 
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 533-00078 Printed in U.S.A. Form 30/48/50-6SI Pg 1 10-06 Replaces: 30G,H,R-1SI
Book 11244
Tab 1a1b5c6a6b
Installation Instructions
Part Number 30GT-911---062
Read these instructions completely before attempting to in-
stall the Navigator Accessory Display Module. The Navigator
module is used on the following units:
CONTENTS
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10, 11
CLEANING, SERVICE, AND MAINTENANCE . . . . . 12
SAFETY CONSIDERATIONS
Installation of this accessory can be hazardous due to sys-
tem pressures, electrical components, and equipment location
(such as a roof or elevated structure).
Only trained, qualified installers and service technicians
should install, start up, and service this equipment.
When installing this accessory, observe precautions in the
literature, labels attached to the equipment, and any other
safety precautions that apply.
Follow all safety codes.
Wear safety glasses and work gloves.
Use care in handling and installing this accessory.
GENERAL
Check Package Contents —
Check the accessory
package for missing parts or shipping damage. If damage is
found, or any part is missing, file a claim with the shipper
immediately. The package contains these instructions, carrying
bag, and the Navigator display module.
The Navigator module is a portable display that conforms to
NEMA (National Electrical Manufacturers Association) 4
specifications for outdoor use in temperatures ranging from
–22 F (–30 C) to 158 F (70 C). The Navigator module can be
used to configure and perform service diagnostics on machines
equipped with Carrier ComfortLink controls.
The Navigator module keypad (see Fig. 1) contains eleven
menu LEDs and one Alarm Status LED, all of which are
red. The Navigator module is capable of displaying four
24-character lines of information on a back-lit liquid crystal
display. The Navigator module has four functional keys: the up
arrow ( ), down arrow ( ), , and
keys.
NOTE: The Navigator module should be removed after use.
There is not sufficient space to store the module in the unit
control panel. The module will NOT fit between the inner
panel and outer cover.
INSTALLATION
1. The Navigator display module is intended to be a mobile
device, so there are no holes in the device for permanent
mounting. The module has a magnetic mount that is
strong enough to hold the device in place on any clean,
dry metal surface.
2. The Navigator module is powered through the
ComfortLink Main Base Board (MBB). The Navigator
module has a modular telephone style (RJ14) connector
and should be connected to a specific terminal block in
the control box as found in Table 1. This device is intend-
ed for use on the LEN (Local Equipment Network) com-
munications bus only. Do NOT connect the Navigator
module to the CCN (Carrier Comfort Network®) con-
nector, as it may damage the device.
3. See Fig. 2-8 for Navigator LEN connection locations in
the units.
4. See Fig. 9 for Communication board details.
UNIT SIZE
30HK 040-060
30HL 050-060
30HW 018-040
30RB 060-390
48AJ,AK,AW,AY 020-060
50AJ,AK,AW,AY 020-060
48PG 03-28
50PG 03-28
48ZG,ZN 030-105
48ZT,ZW,Z6,Z8 075-105
50ZG,ZN,Z2,Z3 030-105
50ZT,ZW,ZX,ZZ,Z6,Z7,Z8,Z9 075-105
To avoid the possibility of electrical shock, open and tag
all disconnects before installing this equipment. Be
aware that there may be more than one disconnect.
ENTER ESCAPE
Air-Cooled Chillers with ComfortLink™ Controls
Water-Cooled Chillers with ComfortLink™ Controls
Rooftop Units with ComfortLink™ Controls
Navigator™ Accessory Display Module
Run Status
Service Test
Temperatures
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
ENTER
ESC
MODE
Alarm Status
Comfort
Link
Fig. 1 — Navigator in Display Mode
a30-3924