Dacor DHW301 Ventilation Hood User Manual


 
7
Problem Solution Guide
Problem May Be Caused By What to Do
Nothing Works. Control
panel is not lit. Blower
system does not work.
Power to hood is off. Turn on power at circuit breaker panel or
fuse box. Check for tripped breaker or
blown fuse.
Hood main power switch is off. Make sure hood main power switch is on
(see page 3 for location).
Power outage. Call electric company.
Hood not connected to electric
power.
Have qualified electrician connect hood to
electric power.
Lights do not work.
Control panel is not lit.
See Nothing Works above.
Light does not work.
Control panel is lit.
Loose light bulb. Check to make sure that both prongs on
the light bulb are inserted into the holes
on the light socket (see page 6).
Light bulb burned out. Replace light bulb (see page 6).
Blower system does not
draw heat and smoke
properly.
Fan set to low setting. See Operating Instructions section.
Filter(s) clogged or dirty. Check filters. Make sure they are com-
pletely clean and not blocked by foreign
objects.
Damper jammed shut or duct
work clogged.
Consult with a qualified installation pro-
fessional.*
Blower system shuts off
by itself.
Normal operation. To conserve energy, the blower automati-
cally turns itself off if it is left on for four
hours continuously.
Blower system does not
work. Control panel not
lit.
See Nothing Works above.
Blower system does not
work. Control panel lit.
Blower system malfunction. Call for service.
* The duct work connected from the range hood to outside the house or building required to vent heat
and smoke is not manufactured, warranted or serviced by Dacor. The customer is responsible for having
a qualified installer install and maintain the duct work.
Before You Call for Service