12
6.1 Technical data
Weight: 41 kg without ventilation duct
Dimensions: 1198 x 560 mm
Electrical connection
Pay attention to the rating plate data.
The mains connecting cable must at least
correspond to the type H 05 VV-F G 0,75.
The appliance must only be connected by an
authorised specialist, paying attention to
the relevant regulations of the power supply
companies and the regional construction
regulations. He must explain to the user how the
appliance can be isolated from the mains whenever
required.
The connector of the connecting cable is connec-
ted to the socket that is located behind the duct
cover on the wall. If this is not possible, it must be
possible to isolate all poles of the appliance from
the mains by way of the domestic fuse, or by means
of accessible isolating device with a contact gap
of at least 3 mm.
If the appliance is to be operated only with the
window open (to ensure adequate incoming air),
you can use the window switch.
A switch (normally open) is fitted on the window. On
the appliance, this switch is connected to the
window switch terminal on the main electronics.
The appliance can now only be operated when the
window is open.
Important: The window switch must only be
connected by an authorised specialist.
Note: The light function works without restriction.
6.2 Installation
The applicable regulations of the energy supply
companies and the regional construction
regulations must be observed when installing
the hood.
The minimum distance from the worktop to the
bottom edge of the wall hood is for electrical
appliances 650 mm and for gas appliances 750 mm.
The wall hood was conceived for the exhaust air
mode. The exhaust air can be routed into a
separate exhaust air shaft or directly into the open
through the outside wall.
It is not allowed to pass the exhaust air into a flue
or exhaust air chimney that is in operation or into a
shaft that is linked to the heating basement. Consult
the chimney sweep responsible for your district
whenever you wish to pass the exhaust air into a
chimney that is not in operation.
During the course of planning, a chimney sweep
must be consulted if a room air-dependent hearth
is operated in the same room as the one in which a
hood is operated in the exhaust air mode. Adequate
incoming air must be ensured. The applicable
construction and safety regulations must be
observed.
Adequate incoming air must be ensured if a wood,
coal, gas or oil heater or an open hearth is operated
in the same room as the one in which the hood is
installed.
Safe operation is possible whenever the partial
vacuum in the place where the firing equipment
is installed does not exceed 4 Pa (0.04 mbar).
This can be achieved whenever the air needed for
combustion is able to enter through openings that
cannot be sealed, for example in doors, windows,
incoming/exhaust air wall boxes or other technical
means.
6. Assembly instructions
AH 360-120 FD xxxx xxxx
AC 220-230V 50Hz 410W xxxx
330W 4x20W