Foster FHG 3L Refrigerator User Manual


 
3
Temperature controller
It is strongly advised that before adjusting any Service Parameters a thorough understanding of the
following instructions should be obtained.
Carel PB00F0HB10
Controller Display and Symbols.
NOTE: When the buttons are pressed a brief audible signal is emitted; this signal can not be disabled.
1. HACCP: Pressing this button displays a sub menu used to access the HACCP parameters (not used by
Foster)
2. ON/OFF: When pressed for more than 5 seconds switches the controller on/off. When OFF the controller
display alternates between “OFF” and the air temperature as read by the air probe.
3. PRG/MUTE: Mutes the audible alarm and deactivates the alarm relay.
: If pressed for more than 1 second the during the reception of the automatic network address
assignment request package, starts the address assignment procedure (not used by Foster).
: If pressed for more than 5 seconds, allows access to the menu for setting the “F” (frequent)
parameters.
: If pressed for more than 5 seconds together with, allows access for setting the “C”
(configuration) Parameters.
: If pressed for more than 5 seconds when switching the instrument ON, activates the procedure for
setting the default parameter values.
: If pressed for more 5 seconds together with, resets any active alarm with manual reset (the message
‘rES ‘ indicates that the alarm has been reset); any delays relating to the alarms are re-activated.
4. UP/CC: If pressed for more than 5 seconds, activates/deactivates the continuous cycle operation (the
message ‘ccE’ and ‘ccE’ indicate, respectively, the start and end of the continuous cycle request).
: If pressed together with, for more than 5 seconds, starts the report printing procedure (provided the
printer interface is connected to the controller).
: If pressed for more than 5 seconds together with, resets any active alarm with manual reset (the
message ‘rES ‘ indicates that the alarm has been reset); any delays relating to the alarms are re-
activated.
5. Light: If pressed for more than 1-second activates/deactivates auxiliary output 2.
6. AUX: If pressed for more than 1-second activates/ deactivates auxiliary output 1.
7. DOWN/DEF: If pressed for mare than 5 seconds, activates/deactivates a manual defrost (the message
‘dFb’ and dFE’ indicate, respectively, the start and end of defrost).
8. SET: If pressed for more than 1 second displays and/or sets the set point.
: If pressed for more than 5 seconds together with , accesses the menu for setting the type ”C”
(configuration) parameters.
: If pressed together with for more than 5 seconds, starts the report printing procedure (provided the