Frigidaire 318205408(0901) Cooktop User Manual


 
ELECTRIC COOKTOP INSTALLATION INSTRUCTIONS
(If your appliance is equipped with a
white neutral conductor.)
This appliance is manufactured with a white neutral
power supply and a frame connected copper wire.
The frame is grounded by connection of grounding
lead to neutral lead at the termination of the
conduit, if used in USA, in a new branch circuit
installation (1996 NEC), mobile home, recreational
vehicles, where local code do not permit grounding
trough the neutral (white) wire or in Canada,
disconnect the white and green lead from each
other and use ground lead to ground unit in
accordance with local codes, connect neutral lead
to branch circuit‑neutral conductor in usual manner
see Figure 5. If your appliance is to be connected
to a 3 wire grounded junction box (US only),
where local code permit connecting the appliance‑
grounding conductor to the neutral (white) see
Figure 4.
NOTE TO ELECTRICIAN:







Where local codes permit connecting the appliance‑
grounding conductor to the neutral (white) wire (US
Only) (see figure 4):
 
 


Electrical connection






Risk of electrical shock (Failure to
heed this warning may result in electrocution or
other serious injury.) This appliance is equipped
with copper lead wire. If connection is made to
aluminum house wiring, use only connectors that
are approved for joining copper and aluminum wire
in accordance with the National Electrical Code
and local code and ordinances. When installing
connectors having screws which bear directly on
the steel and/or aluminum flexible conduit, do no
tighten screws sufficiently to damage the flexible
conduit. Do not over bend or excessively distort
flexible conduit to avoid separation of convolutions
en exposure of internal wires.




Figure 4
3-WIRE GROUNDED JUNCTION BOX
















Figure 5
4-WIRE GROUNDED JUNCTION BOX
















If the appliance is used in a new branch circuit
installation (1996 NEC), mobile home, recreational
vehicle, or where local codes DO NOT permit
grounding through the neutral (white) wire, the
appliance frame MUST NOT be connected to the
neutral wire of the 4‑wire electrical system. (see
figure 5):
 
 



