IMPORTANT SAFETY INSTRUCTIONS
Installation Instructions
For Your Safety
Be sure your oven is installed properly by
a qualified installer or service technician.
Be sure the oven is securely installed in a
cabinet that is firmly attached to the house
structure. Weight on the oven door could
cause the oven to tip and result in injury.
Never allow anyone to climb, sit, stand or
hang on the oven door.
Make sure the cabinets and wall coverings
around the oven can withstand the
temperatures (up to 93°C [200°F])
generated by the oven.
Electrical
Requirements (cont.)
Rating Plate is located on oven side trim,
side front frame or lower front frame.
We recommend you have the electrical wiring
and hookup of your oven connected by a
qualified electrician. After installation, have
the electrician show you where your main
oven disconnect is located.
Check with your local utilities for electrical
codes which apply in your area. Failure to
wire your oven according to governing codes
could result in a hazardous condition. If there
are no local codes, your oven must be wired
and fused to meet the requirements of CAN/
CSA C22.2 No. O-M91 or latest edition.
You must use a three-wire, single-phase A.C.
208Y/120 Volt or 240/120 Volt, 60 hertz
electrical system. If you connect to aluminum
wiring, properly installed connectors approved
for use with aluminum wiring must be used.
WARNING:
The electrical
power to the oven supply line
must be shut off while line
connections are being made. Failure
to do so could result in serious injury
or death.
Rating Plate
Location
Electrical
Requirements
This appliance must be supplied with the proper
voltage and frequency, and connected to an
individual, properly grounded branch circuit,
protected by a circuit breaker or fuse. See the
rating plate located on the oven frame to determine
the rating of the product. Use the chart below to
determine the minimum recommended dedicated
circuit protection.
Recommended
KW Rating KW Rating Circuit Size
240V 208V (Dedicated)
4.8 KW 4.1 KW 20 Amp
4.9 KW–7.2 KW 4.3 KW–6.2 KW 30 Amp
7.3 KW–9.6 KW 6.3 KW–8.3 KW 40 Amp
9.7 KW–12.0 KW 8.4 KW–10.4 KW 50 Amp