Greenheck Fan AX Ventilation Hood User Manual


 
Page Header
39
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
AX 90-275 9 Blades
93
93
94
94
95
91
90
90
93
Pitch Angle º
rpm 5 10 15 20 25 30 35
1770 (Bhp/kW)
5.03/3.75 8.89/6.63 13.0/9.66 17.4/13.0 22.6/16.9 29.1/21.7 37.2/27.8
1170 (Bhp/kW)
1.45/1.08 2.57/1.92 3.74/2.79 5.02/3.75 6.53/4.87 8.41/6.27 10.8/8.02
1450 (kW)
2.06 3.65 5.31 7.13 9.28 11.9 15.3
950 (kW)
0.58 1.03 1.49 2.01 2.61 3.36 4.29
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Inlet Sound
rpm LwA dBA
1770 +11 -0.5
1170 - -11.5
1450 +5 -6.5
950 -5 -16.5
Volume
Total
Pressure
Impeller Diameter = 36.38 inches (924 mm)
Outlet Velocity
ft/min = cfm / 7.22
m/s = m
³
/s / 0.67
Tip Speed
ft/min = rpm X 9.52
m/s = rpm X 2.90
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
39
AX 90-275 9 Blades