Greenheck Fan AX Ventilation Hood User Manual


 
Page Header
53
Performance shown is for installation Type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. The AMCA Certified Ratings
Seal applies to air performance ratings only.
Sound power level ratings are shown in decibels, referred to 10-12 watts calculated per AMCA Standard 301. Values shown are for inlet LwA sound power levels for 100%, 50% and
0% of peak pressure in Installation Type B: Free inlet, Ducted outlet. dBA sound pressure values are weighted with 11.5 dB attenuation for each octave band at 5 feet.
AX 113-533 12 Blades
95
94
95
95
95
93
92
91
96
Pitch Angle º
rpm 5 10 15 20 25 30 35
1170 (Bhp/kW)
7.85/5.86 13.0/9.72 18.1/13.5 23.8/17.8 30.8/23.0 39.3/29.4 50.5/37.7
870 (Bhp/kW)
3.23/2.41 5.36/4.00 7.45/5.56 9.79/7.30 12.7/9.44 16.2/12.1 20.8/15.5
1450 (kW)
11.2 18.5 25.7 33.8 43.7 55.9 71.7
950 (kW)
3.13 5.21 7.24 9.51 12.3 15.7 20.2
Peak Absorbed Power [Bhp/kW (60 Hz), kW (50 Hz)]
Inlet Sound
rpm LwA dBA
1170 +7 -4.5
870 - -11.5
1450 +14 +2.5
950 +3 -8.5
Volume
Total
Pressure
Impeller Diameter = 48.5 inches (1230 mm)
Outlet Velocity
ft/min = cfm / 12.80
m/s = m
³
/s / 1.19
Tip Speed
ft/min = rpm X 12.7
m/s = rpm X 3.87
Sound Power A-Weighted [LwA]
Sound Pressure [dBA]
Air density = 1.2 kg/m
³
Air density = 0.075 lbs/ft
³
53