Heatcraft Refrigeration Products H-IM-82C Refrigerator User Manual


 
15
PRO
3
Top Mount Packaged Refrigeration System | Outdoor
Alarm
Code
Buzzer and Alarm Relay LED Alarm Description Reset
Enable Alarm
parameters involved
E0 active ON probe 1 error= control automatic
E1 not active ON probe 2 error= defrost automatic d0= 0 / 1 / 4, F0= 1
E2 not active ON probe 3 error= condenser/ product automatic [A4=10]
IA active ON external alarm automatic [A4 = 1] [+A7]
dOr active ON open door alarm automatic [A4 = 7/8][+A7]
LO active ON low temperature alarm automatic [AL] [Ad]
HI active ON high temperature alarm automatic [AH] [Ad]
EE not active ON unit parameter error not possible
EF not active ON operating parameter error manual
Ed not active ON defrost ended by timeout on rst defrost ended
correctly
[dP] [dt] [d4] [A8]
dF not active OFF defrost running automatic [d6=0]
cht not active ON dirty condenser pre-alarm automatic [A4=10]
CHt active ON dirty condenser alarm manual [A4=10]
EtC not active ON clock alarm by setting the time if bands active
3. Controllers
Rapid Parameter Set Selction (EZY)
The easy controller features the EZY parameter which is used to
quickly choose a list of parameters, with corresponding values, for
the control of the refrigeration system.
Table of Alarms and Signals
When an alarm is activiated, the display shows the corresponding
message that ashes alternating with the temperature; if tter and
enabled, the buzzer and the alarm relay are also activiated.
All the alarms have automatic reset (that is, they stop when the
causes are no longer present), except for alarm 'CHt' which has
manual reset (instrument on/o using the UP button or by discon-
necting the power supply).
NOTE:
to restore the slected rapid parameter set at any time, turn the
controller o and on again, while holding SET. The desplay shows
"CE" to indicate that the selected rapid set (EZY= 1, 2, 3) has again
over written the operating parameters, thus restoring the original
set of paremters;
to restore all the parameters and return to the original default
values (factory settings), turn the controller o and on again
while holding DOWN and SET, until the display shows "CF". Use
this procedure with extreme car, as it may compromise the
fundamental control settings;
EZY= 0 brings no change
Pressing the SET button mutes the buzzer, while the code displayed
and the alarm relay only go o when the causes of the alarm have
been resolved. The alarm codes are shown in the able below: