Model CBC/CBR-103,104,105,106,107
3-5. PROGRAMMING dS: (defrost system (computation)) dF=digifrost feature;
Continued defrost start time based on total compressor running time.
rt=real time; defrost start frequency, based on real time
dI: (defrost interval) defrost frequency in hours, based on the
selection of “dS”
dE: (defrost endurance) total (maximum) length of a defrost
cycle, expressed in minutes. (1...99 range)
dL: (display lock) temperature display is locked during a
defrost cycle. (0...31 range)
“n”=no (readout continues to display the actual tempera-
ture, even during a defrost cycle
“y”=yes (readout is locked)
dr: (display read-out) select the type of visualization in case of
temperature display lock during defrost (see prameter dL)
“C”=the temperature displayed at the start of a defrost is
locked and does not change during this cycle
“dF”=during the defrost “dF” is displayed
do: (defrost at power on) selects whether or not, the system
goes through the defrost cycle at start-up (or after power
failure)
“n”=no
“y”=yes
dd: (defrost delay at power on) delay of defrost cycle, in
minutes. (0...99 range)
Error Code “E1”
This is the only error code in these controls. It indicates a tempera-
ture sensor failure, such as, a shorted sensor, a sensor break, or
absence of sensor.
It can also indicate an under-range in the system temperature (-55).
In case of an over-range in the system temperature, “99” shows first
in the display, followed by “E1”.
303 3-6