Hill Phoenix ONRBH Refrigerator User Manual


 
C
L
31 9/16 in
[80.2 cm]
(STANDARD)
35 1/8 in
[89.2 cm]
(STANDARD)
**
28 5/8 in
[72.7 cm]
(STANDARD)
39 1/4 in
[99.7 cm]
(STANDARD)
REFRIGERATION
1 1/2 in
[3.8 cm]
{END}
8 11/16 in [22.1 cm]
FRONT OF CASE
NOTES:
** RECOMMENDED STUB-UP CENTERLINE FOR ELECTRICAL AND HUB DRAINS
z SUCTION LINE (ALL LENGTHS) 1/2"
z LIQUID LINE (ALL LENGTHS) - 3/8", LIQUID LINE w/ HOT GAS DEFROST (ALL LENGTHS) - 1/2"
60 in [152.4 cm] {2 Door}
90 in [228.6 cm] {3 Door}
120 in [304.8 cm] {4 Door}
150 in [381.0 cm] {5 Door}
180 in [457.2 cm] {6 Door}
4 in [10.2 cm]
PIPING-TO-TOP
(OPTIONAL)
12 3/4 in [32.4 cm]
3 3/8 in [8.6 cm]
REAR REFRIGERATION
(13 15/16" off of floor)
42 11/16 in
[108.4 cm]
(STANDARD)
27 9/16 in
[70.0 cm]
(NARROW)
**
23 1/4 in
[59.1 cm]
(NARROW)
24 3/16 in
[61.4 cm]
(NARROW)
31 7/8 in
[81.0 cm]
(NARROW)
35 3/8 in
[89.8 cm]
(NARROW)
REFRIGERATION PIPING
14
Refrigeration components and the coil
outlet hole are located to provide the best
access for installation and maintenance. As
the diagrams below indicates, the coil outlet
hole is positioned forward on the right hand
side of the case, fully visible in front of the fan
plenum. An optional piping-to-top configura-
tion can be ordered that runs the refrigeration
lines through the top of the case at the location
shown below. Note that on the narrow six
door case an extra support is present on the
end frames that requires case-to-case piping
to be fed through the opening.
The expansion valve and other con-
trols are located on the left-hand side of the
case, are accessible without lifting the fan
plenum, and may be reached by lifting only
the left hand deck pan.
If it becomes necessary to penetrate
the case bottom make certain it is sealed
afterward with canned-foam sealant and
white RTV.
REMOVE SHIPPING BLOCKS
REMOVE THE SHIPPING BLOCKS
THAT PROTECT THE REFRIGERATION
LINES DURING SHIPMENT BEFORE
OPERATING THE CASE.
CANOPY
FRONT OF CASE
PIPING-TO-TOP
MODEL
ORB, ORBH, ONRB & ONRBH
NARROW 6 DOOR SUPPORT
EXTRA FRAME
SUPPORT
REFRIGERATION LINES
PIPED-TO-TOP