ELECTRICAL CONNECTIONS
WARNING: ELECTRICAL AND GROUNDING CONNECTIONS MUST COMPLY WITH THE
APPLICABLE PORTION OF THE NATIONAL ELECTRICAL CODE AND/OR OTHER LOCAL
ELECTRICAL CODES.
WARNING: DISCONNECT ELECTRICAL POWER SUPPLY AND PLACE A TAG AT THE
DISCONNECT SWITCH INDICATING THAT YOU ARE WORKING ON THE CIRCUIT.
A hole for
3
4" trade size conduit is located at the top of the pedestal. Make electrical connections per
the wiring diagram located on the inside of the Top Cover.
Check Rotation (Three-Phase Machines Only)
Three-phase machines must be connected so the planetary rotates in the direction of the arrow on the
Drip Cup. To check rotation:
Set the gear shift lever on 1.
Apply power to the mixer, set the Electro-Mechanical Timer on HOLD; or, if equipped with a
Programmable Timer Controller, set it on [ -- : -- ]. With the Bowl Support all the way up,
momentarily run the machine by pushing the START and then STOP buttons.
If rotation is incorrect, DISCONNECT ELECTRICAL POWER SUPPLY and interchange any two
of the incoming power supply leads.
ELECTRICAL DATA
Model Volts / Hz / Ph
Rated
Amps
Circuit Size
(Amps)
Fuse Size *
(Amps)
60°C Copper
Wire Size
Circuit Size
(Amps)
Circuit Breaker **
(Amps)
60°C Copper
Wire Size
H600 115 / 60 / 1 19.0 25 25 10 30 30 10
H600 200 / 60 / 1 10.9 15 15 14 20 20 12
H600 230 / 60 / 1 9.5 15 15 14 15 15 14
H600 200 / 60 / 3 5.8 15 10 14 15 10 14
H600 230 / 60 / 3 5.0 15 6 14 15 10 14
H600 460 / 60 / 3 2.5 15 3 14 15 6 14
H600 200 / 60 / 1 14.3 20 20 12 20 20 12
H600 230 / 60 / 1 12.9 20 20 12 20 20 12
H600 200 / 60 / 3 9.2 15 15 14 20 20 12
H600 230 / 60 / 3 8.4 15 10 14 20 20 12
L800 200 / 60 / 1 12.7 20 20 12 20 20 12
L800 230 / 60 / 1 11.0 15 15 14 20 20 12
L800 200 / 60 / 3 6.5 15 10 14 15 15 14
L800 230 / 60 / 3 5.6 15 6 14 15 10 14
L800 460 / 60 / 3 2.8 15 3 14 15 6 14
L800 200 / 60 / 1 16.1 25 25 10 30 30 10
L800 230 / 60 / 1 14.4 20 20 12 25 25 10
L800 200 / 60 / 3 9.9 15 15 14 20 20 12
L800 230 / 60 / 3 9.0 15 15 14 20 20 12
Power Bowl Lift
* Dual Element
Time-Delay Fuse
** Inverse Time
Circuit Breaker
Circuit Size (Minimum) & Fuse / Circuit Breaker Size (Maximum) compiled in accordance with the National Electrical Code (ANSI/NFPA 70), 1993 Edition.