Honeywell VNT5200E1000 Ventilation Hood User Manual


 
Specications(continued)
External Static Pressure Net Supply Air Flow
Gross Air Flow
Supply Exhaust
Pa in. W.C. L/s CFM L/s CFM L/s CFM
25 0.1 92 195 92 196 113 241
50 0.2 85 182 86 183 105 223
75 0.3 80 171 81 172 91 193
100 0.4 73 156 74 157 84 178
125 0.5 65 139 66 140 75 159
150 0.6 59 126 60 127 65 137
175 0.7 56 120 57 120 57 120
200 0.8 50 107 50 107 48 103
225 0.9 45 95 45 96 40 86
250 1.0 37 79 38 80 34 73
Supply Temperature Net Supply Air Flow
Average
Power
Sensible
Recovery
Apparent
Sensible
°C °F L/s CFM Watts Efficiency % Effectiveness %
Heating
0 32 31 66 88 66 78
0 32 42 89 104 64 76
0 32 56 119 114 63 72
-25 -13 32 67 86 59 77
VNT5150H1000VentilationPerformance
VNT5150H1000EnergyPerformance
ERV/HRVVentilationSystems69-2480EF—01 5
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0 50 100 150 200 250
0
25
50
75
100
125
150
175
200
0 10 20 30 40 50 60 70 80 90 100 110
AIR FLOW (CFM)
VNT5150H1000
AIR FLOW (L/S)
EXTERNAL
STATIC
PRESSURE
(PA)
EXTERNAL
STATIC
PRESSURE
(IN. W. C)
M32358
NET SUPPLY AIR FLOW