Fig. 10. Wiring fan for a steam humidifier.
Multi-System Setup Example
Total square feet and bedrooms should be proportionately
split between the ventilation controls based on sq ft served by
each system regardless of where the bedrooms are located.
Example: 5,000 sq ft, six bedrooms:
System 1:
serves 3200 sq ft,
two bedrooms.
fresh air intake measured at 127 cfm.
System 2:
serves 1800 sq ft,
four bedrooms
fresh air intake measured at 98 cfm.
Set W8150 for System 1:
3100 sq ft,
four bedrooms
130 cfm.
Set W8150 for System 2:
1900 sq ft,
two bedrooms
•100 cfm.
CONVERSION TABLE
Wake
Room
System
Fan
Heat
Auto
AM
DST
Tue
W
1
CRW
2
Y
1
Y
2
G
W
1
CR
C
RW
2
Y
1
Y
2
G
M22021A
G
F
R
C
C
C
C
H
W
G
T
HVAC
W8150A
HE440
FAN
R8222
BLACK
BLUE
BLUE
RED
Area Airflow
sq ft sq m cfm lps
1000 93 40 19
1300 121 50 24
1600 149 60 28
1900 177 70 33
2200 204 80 38
2500 232 90 42
2800 260 100 47
3100 288 110 52
3400 316 120 57
3700 344 130 61
4000 372 140 66
4300 399 150 71
4600 427 160 76
Airflow
cfm
6 in. duct
(15.2 cm)
7 in. duct
(17.8 cm)
fpm ms fpm ms
40 204 1.0 150 0.8
50 255 1.3 187 1.0
60 306 1.6 225 1.1
70 357 1.8 262 1.3
80 407 2.1 299 1.5
90 458 2.3 337 1.7
100 509 2.6 374 1.9
110 560 2.8 412 2.1
120 611 3.1 449 2.3
130 662 3.4 486 2.5
140 713 3.6 524 2.7
150 764 3.9 561 2.9
160 815 4.1 599 3.0