Hoshizaki C-101BAH Freezer User Manual


 
24
F. Water Supply and Drain Connections
WARNING
Water supply and drain connections must be installed in accordance with applicable
national, state, and local regulations.
NOTICE
• Normal operating water temperature must be within 45°F to 90°F (7°C to
32°C). Operation of the appliance, for extended periods, outside of this normal
temperature range may affect appliance performance.
• Water supply pressure must be a minimum of 7 PSIG and a maximum of
113PSIG. If the pressure exceeds 113 PSIG, the use of a pressure reducing valve
is required.
• External lters, strainers, or softeners may be required depending on water quality.
Contact your local Hoshizaki Certied Service Representative or local Hoshizaki
distributor for recommendations.
• Connect to potable water supply only. Do not connect to a hot-water supply.
• In areas where water damage is a concern, install in a contained area with a oor
drain.
• Water line installation to the appliance is not warranted by Hoshizaki.
• Water-hammer issues must be resolved by a qualied plumber before installing
the appliance. Water hammer can cause appliance damage that may lead to
water leakage or ooding.
• A minimum of 1/2" nominal ID hard pipe or equivalent is required for the drain
line. Installing a smaller diameter drain line will reduce water ow and may lead to
water leakage or ooding.
• If using the optional drain pump (HS-5061), test its operation every time the
appliance is cleaned and sanitized. See "IV.E. Optional Drain Pump HS-5061" for
details. If the optional drain pump is not operating properly, water could back up
and overow, leading to costly water damage.
Water Supply
Inlet
Minimum Water Supply
Line Size
Drain Outlet Minimum Drain
Line Size
1/2" Female Pipe
Thread (FPT)
1/4" Nominal ID
Copper Water Tubing or
Equivalent
1/2" Female Pipe
Thread (FPT)
1/2" Nominal
ID Hard Pipe or
Equivalent
• A plumbing permit and services of a licensed plumber may be required in some areas.
• A water supply line shut-off valve and drain valve must be installed.
• Be sure there is sufficient extra water supply line and drain line for the appliance to be
pulled out for service.
• Drain line should not be piped directly to the sewer system. An air gap of a minimum of
2vertical inches (5 cm) must be between the end of the drain pipe from the appliance
and the oor drain.