e. Clogged Filter Alarm (E7)
The unit is equipped with a lter for protecting the condenser from dirt, oils, grease, etc.
The lter promotes clean condenser surfaces and efcient operation and should be
checked twice monthly and cleaned when necessary. The unit is also equipped with a
sensor to determine if this lter is excessively dirty. If the unit detects that the condenser
lter is excessively dirty by sensing a temperature at the condenser outlet of at least
136.4°F (58°C) for over  minutes, "E7" will be displayed.
Reset Options
After cleaning the lter, the alarm will automatically reset once the temperature at the
condenser outlet drops below 136.4°F (58°C).
Possible Causes
• The condenser air lter is dirty.
• The condenser fan motor is locked or otherwise not functioning.
IMPORTANT
If this alarm occurs frequently, the compressor discharge temperature is
consistently too high.
Note:
• If the unit is turned off and then back on while the alarm code is displayed, the
alarm may be reset even if the lter is not yet clean. However, the alarm will recur
once the compressor discharge temperature reaches 136.4°F (58°C).