Hoshizaki KMH-2000SRH/3 Ice Maker User Manual


 
18
G. Installation of Remote Condenser Unit
WARNING
1. Installation of remote condenser unit must be performed by properly trained
and EPA-certied service personnel.
2. Failure to install the equipment within these guidelines may adversely affect
safety, performance, component life, and warranty coverage.
1. Checks Before Installation
1) Remove the shipping carton, tape, and packing material.
2) Check that the refrigerant lines do not rub or touch lines or other surfaces, and that the
fan blades move freely.
2. Location
CAUTION
The remote condenser unit is intended for outdoor use. Normal operating
ambient temperature should be within -20°F to +122°F (-29°C to +50°C).
Operation of the remote condenser unit, for extended periods, outside of this
normal temperature range may affect icemaker performance.
The remote condenser unit must be positioned in a permanent site under the following
guidelines:
• A rm and at site.
• A dry and well ventilated area with 24" (61 cm) clearance in both front and rear for
proper air circulation and ease of maintenance and/or service should they be required.
See Fig. 8.
• The maximum line length for the standard refrigerant charge is 66 feet. With additional
refrigerant, the maximum line length is 100 feet. For details, see "II.G.5. Refrigerant
Charge (Line Set Exceeding 66 Feet)."
• The maximum vertical distance between the remote condenser unit and the icemaker
is 33 feet above or 10 feet below the icemaker. These distances are measured tting to
tting. See Fig. 9.
Fig. 8
Air
Min. 24" (61 cm) Clearance
Air
Fig. 9
Icemaker
Remote
Condenser
Unit
Service Loop
Max. 33 Feet