Hoshizaki SRC-10H Ice Maker User Manual


 
11
5. Electrical Connection
This icemaker must have an independent power supply or receptacle of proper capacity.
See the nameplate.
6. Installation of Remote Condensing Unit
[a] Checks Before Installation
1) Unpack and remove shipping carton, tape(s) and packing.
2) Check that the refrigerant lines do not rub or touch lines or other surfaces, and that the fan
blade turns freely.
3) Make sure that the icemaker, line sets and remote condensing unit all use R-404A
refrigerant.
[b] Location
The condensing unit must be positioned in a permanent site under the following
guidelines.
• A firm and flat site.
• A dry and well ventilated area with 24" clearance on both front and rear for ease of
maintenance and service should they be required.
• Normal condenser ambient temperature: -4°F to +122°F. Temperatures not within this
operating range may affect the production capacity of the icemaker.
• The maximum line length is 55 feet. Vertical distance between the condensing unit and
icemaker should not exceed 30 feet above or 10 feet below the icemaker.
Fig. 3
Note: If the recommended installation guidelines are not followed, icemaker
performance may be reduced.