Hoshizaki SWH3-M KM-1601SAH/3 Ice Maker User Manual


 
24
8) Normal Harvest Cycle – Same as the initial harvest cycle. Return to step 5 above.
Note: Appliance continues to cycle until BC is satised or power is turned off. The
appliance always restarts at the 1-min. ll cycle.
9) Shutdown: "E" and "G" Control Board
When the appliance is running, hold ice in contact with the thermostatic bulb. BC
switch opens within 10 sec., shutting down the appliance. BC is factory set, and
generally no adjustment is required. However, adjustment may be needed in some
conditions, particularly at higher altitude locations. Diagnosis: See "II.D. Bin Control
Check." NOTICE!
Donot adjust S4 dip switch 7 out of the factory default
position. This dip switch must be left in the factory default position or the
appliance will not operate correctly.
"G" Control Board: CB red K4connector must have the jumper in place. When the
jumper is in place, the green "BC CLOSED" LED remains on. If the jumper is not in
place, yellow "BC OPEN" LED turns on and the icemaker turns off and remains off
until the jumper is replaced in its original position.
Legend: BC–bin control; CB–control board; CR–compressor relay; CT–control transformer;
Comp–compressor; CV–check valve; FM–fan motor; FMR–fan motor-remote; FS
oat switch; HGV–hot gas valve; HM–headmaster (C.P.R.); HPS–high-pressure
switch; LLV –liquid line valve; MC–magnetic contactor; MT–main transformer;
PM–pump motor; TXV–thermostatic expansion valve; WRV–water regulating valve;
WV–inlet water valve