FLUID RECOMMENDATION
Remcor Chillers are designed to operate with water to provide maximum performance for
temperatures of 40_F100_F.
Distilled Water Acceptable
DeIonized Water
(15 MEG/OHMS)
Acceptable
DeIonized Water
(5+MEG/OHMS)
Acceptable with Stainless Steel & PVC only
*No Copper or Brass
Propylene Glycol
(Lab & Industrial Grade)
Acceptable 30% Glycol/70% Water
*For Applications with Temperatures below 40_F
Lab & Industrial Grade Ethylene Glycol Acceptable 30% Glycol/70% Water
*For Applications with Temperatures below 40_F
Mineral/Hydraulic Oils
(Viscosity<50 Centistrokes)
Acceptable
Ethylene Glycol
(Commercial/Automotive Antifreeze)
NOT Acceptable
*Silicate Rust Inhibitors in Automotive/Commer-
cial Antifreeze will damage pump seals and
housing which lead to failure.
Acidic/Basic Solutions
(Above 8/Below 6 PH)
Not Acceptable
Mineral/Hydraulic Oils
(Viscosity>50 Centistrokes)
Not Acceptable
For questions regarding special or other fluids contact IMI Cornelius Remcor at
8005514423.
To Purchase Lab or Industrial Glycol contact:
Hubbard Hall (800) 6483412 Dow Therm SR1 available in 5 gallon
IMI Cornelius (800) 5514423 Part# 111521000 5 gallons