Manitowoc Ice Q130 Ice Maker User Manual


 
Installation Instructions Section 2
2-2
Part Number 000001130 12/08
Location of Ice Machine
The location selected for the ice machine must meet the
following criteria. If any of these criteria are not met,
select another location.
The location must be indoors.
The location must be free of airborne and other
contaminants.
The air temperature must be at least 40°F (4.4°C),
but must not exceed 110°F (43.4°C).
The location must not be near heat-generating
equipment or in direct sunlight.
The location must be capable of supporting the
weight of the ice machine and a full bin of ice.
The location must allow enough clearance for water,
drain and electrical connections in the rear of the ice
machine.
The location must not obstruct airflow through or
around the ice machine (condenser airflow is in and
out the front). Refer to the chart below for clearance
requirements.
NOTE: The ice machine may be built into a cabinet.
There is no minimum clearance requirement for the top
or left and right sides of the ice machine. The listed
values are recommended for efficient operation and
servicing only.
Ice Machine Heat of Rejection
* B.T.U./Hour
** Because the heat of rejection varies during the ice making cycle, the
figure shown is an average.
Ice machines, like other refrigeration equipment, reject
heat through the condenser. It is helpful to know the
amount of heat rejected by the ice machine when sizing
air conditioning equipment where self-contained air-
cooled ice machines are installed.
Self-Contained
Air-Cooled
Self-Contained
Water-Cooled
Top/Sides 5” (203 mm)* 5” (127 mm)*
Back 5” (127 mm)* 5” (127 mm)*
!
Caution
The ice machine must be protected if it will be
subjected to temperatures below 32°F (0°C).
Failure caused by exposure to freezing
temperatures is not covered by the warranty. See
“Removal from Service/Winterization” Section 4.
Series
Ice Machine
Heat of Rejection*
Air Conditioning** Peak
Q130 2400 2900
Q210 2400 3400
Q270 3800 6000