Manitowoc Ice RF Ice Maker User Manual


 
Installation Instructions Section 2
9
Part Number 000007644 3/11
Maximum Breaker Size & Minimum Circuit Amperage Chart
QUIETQUBE REMOTE CONDENSING UNIT
Important
Due to continuous improvements, this information is for reference only.
Please refer to the ice machine serial number tag to verify electrical data.
Serial tag information overrides information listed on this page.
Series Ice
Machine
Voltage
Phase
Cycle
Air-Cooled Water-Cooled QuietQube
Max
Fuse/
Circuit
Breaker
Min
Circuit
Amps
Total
Circuit
Amps
Max
Fuse/
Circuit
Breaker
Min
Circuit
Amps
Max
Fuse/
Circuit
Breaker
Total
Circuit
Amps
RF0244
115/1/60 15 Amp N/A 7.5 N/A N/A
230/1/50 10 Amp N/A 0.87 N/A N/A
RF0266
115/1/60 15 Amp N/A 7.5 N/A N/A
230/1/50 10 Amp N/A 0.87 N/A N/A
RF0385
115/1/60 15 Amp N/A 10.0 N/A N/A
230/1/50 N/A N/A N/A N/A N/A
RF0388
115/1/60 15 Amp N/A 10.0 N/A N/A
230/1/50 10 Amp N/A 2.9 N/A N/A
RF0399
115/1/60 15 Amp N/A 10.0 N/A N/A
230/1/50 10 Amp N/A 2.9 N/A N/A
RF0644 115/1/60 25 Amp N/A 13.5 N/A N/A
RFS0300 115/1/60 20 Amp 12.8 N/A N/A N/A
RFS0650
115/60/1 25 Amp 16.3 N/A 25 Amp 15.4
208-230/1/60 15 Amp 8.7 N/A 15 Amp 8.2
RF1200
208-230/1/60 15 Amp 15.0 N/A 15 Amp 15.0 15 Amp 1.4
230/1/50 16 Amp 7.3 N/A 16 Amp 7.3 10 Amp 1.4
RF2300
208-230/3/60 20 Amp 15.0 N/A 20 Amp 15.0 15 Amp 3.2
400-415/3/50 16 Amp 13.9 N/A 16 Amp 13.9 10 Amp 3.2
RF1200R 208-230/1/60 15 Amp 1.4 N/A N/A N/A
RF2300R 208-230/3/60 15 Amp 3.2 N/A N/A N/A
Maximum allowable voltage variation at compressor start-up is ±10% of voltage listed above and on the model/serial plate.
Condensing Unit Voltage Phase Cycle Maximum Fuse/Circuit Breaker Minimum Circuit Amps
RCU1075
208-230/60/1 15 15
208-230/60/3
15 15
208-230/50/1
15 15
RCU2375
208-230/60/1 15 15
208-230/60/3
15 15
208-230/50/1
15 15