Miele 09 704 870 Ventilation Hood User Manual


 
Installation
29
a
Extraction
b
Recirculation
c
Ventilation grille positioned at the top for recirculation
de
(only d is required for recirculation mode cooker hoods): The shaded area
represents the wall or ceiling area for the vent cut-out, for fitting the
connection socket and on EXT models for feeding the connection cable
through to the external motor. Recirculation mode cooker hoods only require
an electrical connection socket.
Connection for air extraction 150 mm, or 125 mm with reducing collar.
Safety distance between hob and cooker hood (S)
When planning the installation height of your cooker hood, the minimum safety
distance between the top of a cooker or hob and the bottom of the cooker
hood is as follows, unless a greater distance is specified by the manufacturer of
your cooking appliance.
See "Warning and Safety" instructions for further information.
Cooking appliance Minimum distance S
Electric hob 450 mm
Electric grill, deep fat fryer (electric) 650 mm
Multi-burner gas hob,
total output 12.6 kW, no burner > 4.5 kW
650 mm
Multi-burner gas hob,
total output > 12.6 kW and 21.6 kW,
no burner > 4.8 kW.
760 mm
Multi-burner gas hob,
total output > 21.6 kW,
or multi-burner gas hob where one burner > 4.8 kW.
Not possible
Single burner gas hob, output 6 kW. 650 mm
Single burner gas hob, output > 6 kW and 8.1 kW. 760 mm
Single burner gas hob, output > 8.1 kW Not possible