Schneider Electric ACRC502 Water Dispenser User Manual


 
InRow RC Operation and Maintenance Manual16
Identify the cooling unit
Path: Main > Set Identification
The Set Identification menu contains settings that identify the name and location of the cooling unit.
Unit Id: Assign a unique identification number to this cooling unit. Range: 1 through 12.
Name: Assign a Name, up to 40 alpha-numeric characters, to the cooling unit.
Location: Enter the Location, up to 40 alpha-numeric characters, of the cooling unit.
NOTE: Only the first 19 characters (of the 40 that are possible to enter) will display on the display interface.
You must use Telnet, the Control console or the Web to access all 40 characters. See “Web interface” on
page 35 for more information.
Configure Modbus
Path: Main > Configure Modbus
Use the Configure Modbus menu to set up communications between the cooling unit and the building
management system.
Modbus: Enable or disable Modbus communication protocol.
Target Id: Each Modbus device must have a unique target identification number. Enter a unique number for
this cooling unit.
Baud Rate: Set either 9600 bps or 19200 bps.
Fixed settings: 8 data bits, no parity, 1 stop bit. These settings cannot be modified.