Sterling 882.93092.01 Refrigerator User Manual


 
GP Series Portable Chillers Chapter 3: Installation 19 of 90
Figure 3: Typical GP20-50 Water Cooled Condenser Connections
Air-Cooled Chiller Condensers
Air-cooled chillers use the surrounding air to cool the condenser. Install the chiller in an area
where there is free passage of air for condensing and provisions for removal of heated air
from the area. Do not locate air-cooled chillers in locations where steam, hot air, or fume
exhausts can be drawn into the chiller.
Caution! Clean air-cooled condensers and filters frequently. Failure to do so results in
reduced capacity, increased operating costs, and possible failure of the
equipment. Cleaning instructions can be found in the Maintenance chapter of
this manual
Normal maximum refrigerant condensing pressure with 95ºF (35ºC) air entering the
condenser is 420 psi (2896 kPa).
Condensing Air Temperature. Our air-cooled portable chillers are designed to operate at a
minimum condenser entering air temperature of approximately 75ºF (24ºC). Operation of the
equipment at a lower condenser entering air temperature can cause the chiller to malfunction.
For entering air temperatures below 75ºF (24°C), an optional fan motor speed control is
available. We recommend maintaining a minimum 75ºF (24°C) ambient temperature.
Note: For all chillers manufactured with Variable Frequency Drives the
voltage may vary up to 10% from the converter nominal voltage.
However, the phase-to-phase input voltage imbalance must not
exceed 3%. If the input voltage does have an imbalance from phase
to phase greater than 3% then a line reactor must be installed to
prevent faults within the VFD.
For remote condenser units, the maximum recommended motor
cable length between the VFD and the motor without output chokes
is 30 m (100 ft). With output chokes the motor cable length may be
extended to 65 m (195 ft).