2-40 HP Portable Chillers Chapter 3: Installation 22 of 70
Figure 2: Equivalent Length in Feet for Valves and Fittings
Line Size
Inches OD
Globe Valve
Equivalent Ft
Angle Valve
Equivalent Ft
Short Radius Elbow
Equivalent Ft
Long Radius Elbow
Equivalent Ft
1/2” 43 15 1.4 0.9
5/8” 55 18 1.6 1.0
7/8” 69 24 2.0 1.4
1 1/8” 87 29 2.7 1.9
1 3/8” 102 33 3.2 2.2
1 5/8’ 115 34 3.8 2.6
2 1/8” 141 39 5.2 3.4
2 5/8” 159 44 6.5 4.2
Figure 3: Liquid Line Sizing
30 – 65°F Leaving Water Temperature
Liquid Line Size (O.D.”)
Eqiv. FT 5 hp 7.5 hp 10 hp 15 hp 20 hp 25 hp 30 hp 35 hp 40 hp
25 5/8 5/8 5/8 7/8 7/8 7/8 7/8 1 1/8 1 1/8
50 5/8 5/8 5/8 7/8 7/8 7/8 7/8 1 1/8 1 1/8
75 5/8 5/8 5/8 7/8 7/8 7/8 7/8 1 1/8 1 1/8
100 5/8 5/8 5/8 7/8 7/8 7/8 7/8 1 1/8 1 1/8
125 5/8 5/8 7/8 7/8 7/8 7/8 1 1/8 1 1/8 1 1/8
150 5/8 5/8 7/8 7/8 7/8 1 1/8 1 1/8 1 1/8 1 1/8
175 5/8 5/8 7/8 7/8 7/8 1 1/8 1 1/8 1 1/8 1 1/8
200 5/8 5/8 7/8 7/8 7/8 1 1/8 1 1/8 1 1/8 1 1/8
225 5/8 5/8 7/8 7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8
250 5/8 5/8 7/8 7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8
275 5/8 5/8 7/8 7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8
300 5/8 5/8 7/8 7/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8
Figure 4: Discharge Line Sizing
30 – 65°F Leaving Water Temperature
Discharge Line Size (O.D.”)
Eqiv. FT 5 hp 7.5 hp 10 hp 15 hp 20 hp 25 hp 30 hp 35 hp 40 hp
25 7/8 1 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8
50 7/8 1 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8
75 7/8 1 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8
100 7/8 1 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8
125 7/8 1 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8
150 7/8 1 1/8 1 1/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8
175 1 1/8 1 1/8 1 1/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8
200 1 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8
225 1 1/8 1 1/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8
250 1 1/8 1 1/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8
275 1 1/8 1 1/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8
300 1 1/8 1 1/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8