2-40 HP Portable Chillers Chapter 7: Appendix 63 of 70
7-6 Typical Ductwork for Air-Cooled Chillers
*See specification tables on pages 45-48 for air flow and pressure capacities.
When locating your air-cooled portable chiller and designing its ductwork, note any potential high
temperature conditions when discharging into your building and any negative pressures with the building
when discharging air outside.
Notes: Customer use of ductwork requires the high pressure fan option for models 5 through 15 hp.
Allow 30” (77 cm) minimum clearance around the chiller footprint to facilitate free passage of cooling air
and service accessibility Size the ductwork for maximum capacity Support ductwork from the
building structure, not off of the chiller Back draft damper to outside must be closed at all times when
fan/blower is not operating Chillers with dual fans/blower must have a back draft damper on the cycling
fan/blower to prevent recirculation of hot discharge air Chillers are designed to operate at a condensing
entering air temperature of 60ºF (16ºC) minimum Maximum total static pressure drop external to the
chiller must not exceed 0.30” WG (75 pa)