Stoelting SC118 Freezer User Manual


 
11
SECTION 5
SEQUENCE OF OPERATIONS
5.1 LIGHTS
On/Off light switch is independent of all other switches.
When on, the light transformer is operational and the lights
illuminate.
5.2 SWITCHES
On/Off/Clean Mode
Switch Switch
Position Position Sequence of Operations
Clean Serve -Drive Motor and Condenser Fan Motor start and run together,
or No time limit exists.
Standby -Power Transformer, torque switch, compressor, liquid level
control, and mix low light are non-operational.
On Serve -Drive Motor and Condenser Fan start and run together
continuously.
-Power Transformer is on.
-Liquid level control and mix low light are operational.
-With liquid mix or loose slush in the freezing cylinder, the torque
switch is closed. The delay-on-make timer starts the compressor
after a 10-30 second delay.
-When the slush reaches consistency, the torque switch opens
and the compressor immediately shuts off. The drive motor and
condenser fan motor continue to run.
On Standby -Power transformer, liquid level control and mix low light are
operational only when the temperature control is closed.
-Drive motor, condenser fan motor, and compressor cycle on and
off with the temperature control (compressor start delays 10-30
seconds).
NOTE
If the temperature control is set too cold, control will default to the torque switch to prevent freeeze-up.
5.3 SAFETY SWITCH
Door Switch - If the front door is removed, the freezer will not function.
Motor Internal Thermostat - If the motor overheats, the freezer will not function.
Warning - The motor internal thermostat automatically resets as the motor cools. The freezer will automatically
restart. Disconnect freezer from power source for servicing.
High Pressure Cutout Switch - If the compressor discharge pressure exceeds 470 PSIG, the freezer will not
function.