Thermador PCG30 Cooktop User Manual


 
English 4
Consider Make-Up Air:
Due to the high volume of ventilation air, a source of
outside replacement air is recommended. This is
particularly important for tightly sealed and insulated
homes.
A qualified heating and ventilating contractor should be
consulted.
NOTE:
Ventilation hoods and blowers are designed for use with
single-wall ducting. Some local building codes may require
double-wall ducting. Before starting installation, consult
local building codes and agencies to insure that the
installation will meet local requirements.
Cooktop
Width
Cooktop
Configuration
Minimum Recommended
Blower Capacity*
Ventilation Options
30” 4 burners 800 CFM
30” or 36” Pro Wall Hood
30” or 36” Custom Insert w/ optional blower
42” Island Hood w/ optional blower
36”
4 burners with griddle 1000 CFM 36” or 42” Pro Wall Hood
36” Custom Insert w/ optional blower
42” or 48” Island Hood w/ optional blower
6 burners 1100 CFM
48” 6 burners with griddle 1300 CFM
48”** or 54” Pro Wall Hood
48” Custom Insert w/ optional blower
54” Island Hood w/ optional blower
Important Notes:
It is recommended that a Thermador Professional wall or island hood or custom insert is used with Thermador
Professional Cooktops.
Refer to www.Thermador.com for a complete selection of Professional Ventilation options, Blowers, and
Accessories.
* For high output gas cooktops (60,000 BTU or greater), the minimum of one (1) CFM of ventilation per 100 BTU is
recommended. If the cooktop has a griddle, add 200 CFM to the estimated blower capacity. Additional blower
capacity may be required for longer duct runs.
For island applications, it is recommended to use a hood width that exceeds the width of the cooktop by 6”
(overlapping the cooktop by 3” on each end).
**Not all 48” Pro Wall Hood models can accommodate a 1300 CFM blower option.
CFM = “cubic feet per minute” (standard blower capacity rating).