Trane CCAF Refrigerator User Manual


 
23
CG-PRC012-EN
Table PD-5. Part-load performance for CGWF 20-60 ton – 60 Hz in English units
Unit Size 100% IPLV
Tons 19.9
20 kW 15.2 20.3
EER 15.5
Tons 24.5
25 kW 19.0 20.5
EER 15.4
Tons 29.2
30 kW 22.8 20.3
EER 15.3
Tons 39.4
40 kW 30.1 20.7
EER 15.6
Tons 48.6
50 kW 37.6 19.6
EER 15.4
Tons 59.4
60 kW 46.5 19.8
EER 15.2
Notes:
1. IPLV values are rated in accordance with ARI Standard 550/590-98.
2. EER and IPLV values include compressor and control kW.
3. kW input is for compressors only.
Table PD-6. Part-load performance for CGWF 20-60 ton – 50 Hz in English units
Unit Size 100% IPLV
Tons 16.7
20 kW 12.4 21.0
EER 16.1
Tons 20.6
25 kW 15.5 20.9
EER 16.0
Tons 24.5
30 kW 18.5 20.7
EER 15.9
Tons 33.0
40 kW 24.5 21.3
EER 16.2
Tons 40.8
50 kW 30.6 20.3
EER 16.0
Tons 50.1
60 kW 37.6 20.4
EER 16.0
Notes:
1. IPLV values are rated in accordance with ARI Standard 550/590-98.
2. EER and IPLV values include compressor and control kW.
3. kW input is for compressors only.
Part Load
Performance
Performance
Data