WIRING :
10. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC),
STATE, AND LOCAL REQUIREMENTS. OUTSIDE THE UNITED STATES, OTHER COUNTRIES
APPLICABLE NATIONAL AND/OR LOCAL REQUIREMENTS SHALL APPLY.
REQUIRED WIRING:
11 COPPER WIRE ONLY - SIZED PER N.E.C. - BASED ON NAMEPLATE RLA. SEE CUSTOMER WIRE
SELECTION TABLE.
12 2 WIRES, 115 VAC CIRCUIT. MINIMUM CONTACT RATING AT 115 VAC - 6.9 VA INRUSH. 1.3 VA
SEALED.
13 CCAD UNITS WITH AIR COOLED CONDENSER ONLY. 2 WIRES, 30 VOLT OR LESS CIRCUIT. DO NOT
RUN IN CONDUIT WITH HIGHER VOLTAGE CIRCUITS. SEE CUSTOMER WIRE SELECTION TABLE.
OPTIONAL WIRING:
14 3 WIRES. 115 VAC CIRCUIT. SEPARATE 115 VAC POWER SUPPLY IS REQUIRED. LOAD NOT TO
EXCEED 115 VA SEALED, 1150 VA INRUSH.
16 2 WIRES. 115 VAC CIRCUIT. MINIMUM CONTACT RATING AT 115 VAC - 6.9 VA INRUSH, 1.3 VA
SEALED.
17 3 WIRES ON 20-30 TON UNITS. 6 WIRES ON 40-60 TON UNITS. 115 VAC CIRCUIT. SEPARATE 115
VAC POWER SUPPLY REQUIRED. LOAD NOT TO EXCEED 115 VA SEALED, 1150 VA INRUSH.
18 2 WIRES. 115 VAC CIRCUIT. SEPARATE 115 VAC POWER SUPPLY IS REQUIRED. LOAD NOT TO
EXCEED 1150 VA INRUSH, 115 VA SEALED.
19 2 WIRES. 30 VOLT OR LESS CIRCUIT. DO NOT RUN IN CONDUIT WITH HIGHER VOLTAGE
CIRCUITS. SEE CUSTOMER WIRE SELECTION TABLE.
20 SHIELDED TWISTED PAIR, 30 V OR LESS CIRCUIT. MAXIMUM LENGTH 5000 FT. DO NOT RUN IN
CONDUIT WITH HIGHER VOLTAGE WIRE. SEE CUSTOMER WIRE SELECTION TABLE.
22 CUSTOMER SUPPLIED CONTACTS MUST BE COMPATIBLE WITH DRY CIRCUIT 12 VDC, 45 mA
RESISTIVE LOAD. SILVER OR GOLD PLATED CONTACTS ARE RECOMMENDED.
23 SENSOR LEADS TO REACH CONTROL PANEL. 30 VOLT OR LESS CIRCUIT. DO NOT RUN IN
CONDUIT WITH HIGHER VOLTAGE CIRCUITS.